Note: These specifications relate to the KnowzNet™ control panel only. For
sensing parameters such as sensing range, accuracy, resolution, response time,
operating conditions, etc., please refer the datasheet of the sensor
head of interest.
|
PARAMETER |
SPECIFICATION |
COMMENT |
Number of ports: |
8 |
|
Input range: |
0 to 5VDC |
|
Sampling rate: |
1,000 samples/second |
|
Sampling resolution: |
8 bits |
|
Sampling accuracy: |
˝ LSB |
|
Action levels: |
1 to 4 |
Number/level are user-programmable |
Action levels affect: |
LEDs/Beeper/Relay(s) |
User-programmable |
Display update rate: |
0.1 seconds |
|
Start-up time: |
60 seconds |
Warm-up time for sensors with heaters |
Port indicator lamps: |
8 bicolor LEDs |
Red/green |
Text display: |
2 line x 8 LCD |
31 x 14 mm viewing area |
Operator keypad: |
Up/Down/Select/Clear |
Pushbutton switches |
Port connectors:
|
RJ-11 (6-4) 3.5mm terminal block Hirose DF3 2mm |
Default Optional Optional |
Panel beeper: |
80dB @30cm piezzo |
|
Master relay: |
0.5A 120VAC 1.0A 24VDC |
DPDT (double NO/NC contacts) |
Zone relays: |
0.5A SPST Reed |
Optional, one per port, NO or NC |
Relay contacts access: |
3.5mm terminal blocks |
|
Serial PC interface: |
4,800 BPS |
DB9 female, half duplex |
USB PC interface: |
12,000 BPS |
USB 1.0 compatible |
PC Ports I/O Protocol: |
Neodym proprietary |
|
Power jacks: |
2.1mm radial (2) |
Center negative |
Back-up battery input: |
4-pin Molex |
|
Storage temperature: |
-40°C to +85°C |
|
Operating temperature: |
0°C to +70°C |
|
Operating humidity: |
0 to 95% |
Non-condensing |
Input power voltage: |
12 to 14 VDC 12 to 40 VDC 12 to 60 VDC |
Default Optional Optional |
Power supply ripple: |
250 mV max. |
|
Power consumption: |
150 mA @ 12 VDC |
Panel only, not including sensors |
Port power budget: |
200 mA @ 12 VDC |
Per sensor. 1.6A total power max. |
Port power current limiting: |
1.2A @ 12 VDC |
10-ohm current limiting resistor |
Cable type: |
18-24 SWG |
Telephone, Station or Cat. II+ cable |
Cable length: |
100m max. |
Voltage drop not to exceed 4 VDC |
Electrical rating: |
Non-incendiary |
Not for use in Hazardous Locations Approved AC adapters only |
Dimensions: |
216 x 147 x 25 mm |
|
Weight: |
250g |
|
|
|